System composition: cabinet+resistive simulated load+heat dissipation device+control module+display+protection
Nameplate capacity: 400kW
Rated voltage: AC380V
Usage frequency: 50/60Hz
Operating voltage: AC0V-AC415V
Rated current: 577A
Loading accuracy: ± 3%
Load connection method: three-phase four wire system
Gear step: 1kW
Parameter measurement accuracy parameters: voltage, current, frequency, power, power factor
Display accuracy level 0.5,
The sampling accuracy of the instrument is 0.5 level.
Insulation level F
Continuous working mode
Working power supply AC380V, 50Hz, 3P5W.
Cooling method: forced air cooling (side down air inlet, top back air outlet)
The load step can be adjusted arbitrarily from 1kW to 400kW, with a minimum adjustable power of 1KW.
Operation mode: Touch screen manual control/upper computer control, Ethernet connected to remote system control.
The control logic can be loaded by inputting the required power by the user, and the loading logic can also be modified according to the user's requirements.
The communication protocol TCP communication interface uses the standard Modbus-TCP protocol, and the specific address definition can be found in 5 Communication Control
Parameter display displays voltage, current, power, and inlet/outlet temperature
Protection functions short circuit, overvoltage, overcurrent, high temperature, phase sequence, air volume, emergency shutdown protection
Conventional design working noise ≤ 85dB (3M)
Size W1100mm * D1000mm * H1900mm
Weight 450kg
Box color: stainless steel natural color
The mobile mode box has load-bearing lifting holes and car insertion sockets, which meet the conditions for long-distance transportation by car;
The incoming circuit breaker is equipped with two incoming circuit breakers, with equal load sharing.
Box material: stainless steel
Protection level for indoor use, control room IP20, ventilation duct IP54, and isolation between control room and ventilation duct.
The resistance unit is salt spray resistant and waterproof to IP56, suitable for marine salt spray environments.
Operating environment temperature -15 ℃~+55 ℃
Use altitude ≤ 2000 meters
Relative humidity ≤ 95% RH
Atmospheric pressure 86-106Kpa
Shock absorption and
Anti vibration measures: Each component adopts anti loosening measures such as spring frame washers.