The containerized resistive load bank features a user-friendly control interface, allowing operators to easily set and monitor load levels, track performance metrics, and conduct tests in a safe and controlled environment. With power ratings ranging from 500 kW to 6 MW, this versatile unit is suitable for a wide range of applications, from routine maintenance to factory acceptance testing. The containerized design enables easy transportation, deployment, and storage, making it ideal for both on-site and off-site testing scenarios.
High Precision and Reliability:
Provides accurate and stable load testing to ensure the reliability and efficiency of power systems.
Helps identify potential issues before they cause critical failures.
Portability and Flexibility:
Housed in a durable, weather-resistant container, the load bank is easily transportable, allowing for quick deployment at various locations.
Suitable for a wide range of testing applications, from small-scale maintenance checks to large-scale performance evaluations.
User-Friendly Interface:
Equipped with an intuitive control system for easy operation and monitoring.
Allows operators to conduct tests with minimal setup time and effort.
Safety and Compliance:
Designed with multiple safety features, including emergency stop buttons, over-temperature protection, and fault indicators.
Complies with international standards for safety and performance, ensuring secure and dependable operation.
Cost-Effective Maintenance:
Enables proactive maintenance by simulating real-world load conditions, reducing the risk of unexpected downtime and costly repairs.
Extends the life of power systems by ensuring they are always tested under optimal conditions.
Scalability:
Available in various power ratings to meet specific testing requirements.
Can be integrated with additional load banks for larger systems, providing scalability as your testing needs grow.
Name | Container medium voltage pure resistance load -R | ||||||||
Model | IMAX4510-1000k | IMAX4510-2000k | IMAX4510-2500k | IMAX4510-3000k | IMAX4510-4000k | IMAX4510-5000k | |||
Rated Voltage | 3P4W,AC6.3kV/6.6kV/10kV/11kV/13.8kV | ||||||||
Resistive Power | 1000kW | 2000kW | 2500kW | 3000kW | 4000kW | 5000kW | |||
Rated Frequency | 50/60Hz | ||||||||
Loading Mode | Step loading | ||||||||
power factor | 1 | ||||||||
Load Stepping | The minimum step size of the resistance divider is 10kW | ||||||||
Main test items | Power supply detection long - term load, switching device life test | ||||||||
Protection Alarm | Load short circuit, over current protection, over voltage protection, high temperature fault, wind pressure protection, emergency stop and other protection functions | ||||||||
Measurement and Control Parameter | Display voltage, current, active power, reactive power, apparent power, power factor, frequency and other basic functions. | ||||||||
Noise | ≤85dB | ≤86dB | ≤88dB | ||||||
Air Outlet Mode | Wind in from the side down and out from the top. | ||||||||
Display Accuracy | 0.1V,0.1A | ||||||||
Control Mode | Local manual control: through the load bank 7 inch LCD touch screen. | ||||||||
Remote intelligent control: RS485/CAN/ Ethernet | Remote intelligent control: RS485/CAN/ Ethernet | ||||||||
Place of Use | Indoor | Indoor/Outdoor | |||||||
Weight | 3500kg | 4200kg | 6500kg | 7500kg | 9200kg | 11500kg | |||
Size | L2991mm×W2438mm×H2896mm | L6058mm×W2438mm×H2896mm | L7500mm×W2438mm×H2896mm | L9000mm×W2438mm×H2896mm | L12192mm×W2438mm×H2896mm |
Name | Container medium voltage resistance inductive load -RL | |||
Model | IMAX4130-1500k | IMAX4130-2000k | IMAX4130-3000k | IMAX4130-4000k |
Rated Voltage | 3P4W,AC6.3kV/6.6kV/10kV/11kV/13.8kV | |||
Resistive Power | 1200kW | 1600kW | 2400kW | 3200kW |
Inductive power | 900kVar | 1200kVar | 1800kVar | 2400kVar |
Rated Frequency | 50/60Hz | |||
Loading Mode | Step loading | |||
power factor | 0.8-1 | |||
Load Stepping | The minimum dividing step is 10kW/7.5kVar | |||
Main test items | Generator set testing | |||
Protection Alarm | Load short circuit, over current protection, over voltage protection, high temperature fault, wind pressure protection, emergency stop and other protection functions | |||
Measurement and Control Parameter | Display voltage, current, active power, reactive power, apparent power, power factor, frequency and other basic functions. | |||
Noise | ≤85dB | ≤86dB | ||
Air Outlet Mode | Wind in from the side down and out from the top. | |||
Display Accuracy | 0.1V,0.1A | |||
Control Mode | Local manual control: through the load bank 7 inch LCD touch screen. | |||
Remote intelligent control: RS485/CAN/ Ethernet | Remote intelligent control: RS485/CAN/ Ethernet | |||
Place of Use | Indoor | Indoor/Outdoor | ||
Weight | 9500kg | 14000kg | 16500kg | 19000kg |
Size | L4500mm×W2438mm×H2896mm | L9000mm×W2438mm×H2896mm 9m container | L12192mm×W2438mm×H2896mm |
Name |
Pressure resistance capacity load in container -RC
| ||||
Model | IMAX4130-1500k | IMAX4130-2000k | IMAX4130-3000k | IMAX4130-4000k | |
Rated Voltage | 3P4W,AC6.3kV/6.6kV/10kV/11kV/13.8kV | ||||
Resistive Power | 1200kW | 1600kW | 2400kW | 3200kW | |
Inductive power | 900kVar | 1200kVar | 1800kVar | 2400kVar | |
Rated Frequency | 50/60Hz | ||||
Loading Mode | Step loading | ||||
power factor | 0.8-1 | ||||
Load Stepping | The minimum dividing step is 10kW/7.5kVar | ||||
Main test items | Generator set testing | ||||
Protection Alarm | Load short circuit, over current protection, over voltage protection, high temperature fault, wind pressure protection, emergency stop and other protection functions | ||||
Measurement and Control Parameter | Display voltage, current, active power, reactive power, apparent power, power factor, frequency and other basic functions. | ||||
Noise | ≤85dB | ≤86dB | |||
Air Outlet Mode | Wind in from the side down and out from the top | ||||
Display Accuracy | 0.1V,0.1A | ||||
Control Mode | Local manual control: through the load bank 7 inch LCD touch screen. | ||||
Remote intelligent control: RS485/CAN/ Ethernet | Remote intelligent control: RS485/CAN/ Ethernet | ||||
Place of Use | Indoor | Indoor/Outdoor | |||
Weight | 9500kg | 14000kg | 16500kg | 19000kg | |
Size | L4500mm×W2438mm×H2896mm 4.5m container | L9000mm×W2438mm×H2896mm 9m container | L12192mm×W2438mm×H2896mm |