The IMAX1005-5KW is a 19" rack mounted load bank designed to simulate IT server operation aspart of the testing and commissioning of the data hall and electrical power load testing of DC UPS system or Rectifier. The unit incorporating light weight, force cooled high powerresistor elements. Adjustment of the load current is provided by front panel switch selection.The load bank incorporates several safety features, All units are light weight, robust, portableand carrying handles. The fan supply and the controls are powered from the power testsource and therefore the unit does not require an external auxiliary mains supply.
Product name | 48VDC (5KW) Rack Mounted Load Bank |
Use | The 5kW rack-mounted load banks are used for IST commissioning in data center & dataroom. Testing both electrical metwork & airconditioning (tree cooling, etc.]. the rackmounted load bank is simulating exact electrical & air conditioning impact of servers in therack cabinet 19 |
Model number | IMAX1005-5KW |
Electrical characteristics | |
capacity | 5KW Resistive load |
Nominal Voltage | 48VDC (105Amps) |
Maximum Woltage | 54VDC (100Amps) |
Control switches | Main control switch with indication (green) |
Fan Control (Optional) | |
MCB | |
Display | Voltage, Amps etc.. |
Load steps | 5A, 10A, 15A. 25A, 25A, 25A with Indication (green) |
Minimum Step | 5Amps |
Air flow | 744 Max (CFM) |
Fan Supply | Internal |
Protection | lP23 |
Duty cycle | Continuous (Max 105Amps @ 48VDC and 100Amps @ 54VDC) |
Connection | 4 sockelts (Rear) |
Operation Temperature | 0 to 40*C |
Storage Temperature | 0 to 6o*c |
Ventilation | |
Cooling | 4 low noises, horizontal force air cooling fans, powered from the test sourceEach fan 186 CFM total 744 CFM |
Air flow | Air is sucked in the front and blown out horizontally at the rear. |
Thermal protection | Klixon on 85*c |
Security | Red light alert (Over temperature) |
Auto shutoff load in the event of fan power supply failure | |
Each Load channels protected with MCB | |
Mechanical characteristics | |
Technology | Expanded metal grids type insulated by ceramic rings |
Housing | Steel |
Height | Maximum 6U |
Weight | Maximum 26kg |
Movement | Front handles for slide in assembly to 19" rack |
Lengthywidth | Should be rack mounted inside Telecommunication 42U cabinet |
Element Type | High temperature ni chrome finned resistor elements |