Views: 0 Author: Site Editor Publish Time: 2023-09-04 Origin: Site
The IMAX1107-7KW is a 19" rack mounted load bank designed to simulate IT server operation aspart of the testing and commissioning of the data hall and single phase power load testing of AC generators or UPS Systems. The unit incorporating light weight, force cooled high powerresistor elements. Adjustment of the load current is provided by front panel switch selection.The load bank incorporates several safety features. All units are light weight, robust, portableand carrving handles. The fan supply and the controls are powered from the power testsource and therefore the unit does not require an external auxiliary mains supply.
Product name | 230VAC-7kW Rack ounted l oad Bank |
Use | The 7kW rack-mounted dual source AC load banks are used for IST commissioning in datacenter & data room. Testing both electrical network (UPS, Diesel generator, etc.) & airconditioning (free cooling, etc.), the rack-mounted load bank is simulating exact electrica & air conditioning impact of servers in the rack cabinet 19 |
Model number | IMAX1107-7KW |
Electrical characteristics | |
Capacity | 7kW resistive load |
Design voltage | 400/230VAC,3/1Ph, 50/60 Hz (Voltage+5%Acceptable) |
Full load rating | Nominal: 7000W 30.4Amp @ 230VAC(Ph),10.10Amp @ 400VAC (3Ph) |
Control switches | Main control switch with indication (Red) |
Source ON/OFF switch with indication (Green) | |
Source Selector (Auto/Manual) | |
Load adjust | MCB (Schneider) for step control |
Load steps | 500W/500W/1000W/1000W/2000W/2000W |
Minimum Step | 500W |
Input Source | Dual |
Source Selection | Auto or Manual |
Fan working source | Internal from testing power source |
Protection | IP23 |
Duty cycle Connection | Continuous |
Operation | 3 x C20 panel sockets "2Set |
Temperature Storage | 0 to 40°C |
Temperature | 0 to 60°C |
Ventilation | |
Cooling | Air is sucked in the front and blown out horizontally at the rear. |
Air flow | Klixon on 85°C |
Thermal protection | Red light alert (Over temperature) |
Security | Auto shutoff load in the event of fan power supply failureEach load channels protected with MCB |
Cooling | Air is sucked in the front and blown out horizontally at the rear. |
Air flow | Klixon on 85°C |
Mechanical characteristics | |
Technology | Expanded metal grids type insulated by ceramic rings |
Housing | Steel |
Height | Maximum 6U |
Weight | Maximum 30kg |
Movement | Front handles for slide in assembly to 19" rack |
Length/Width | Should be rack mounted inside Telecommunication 42U cabinet |
Element Type | High temperature ni chrome finned resistor elements |