Introduction

The IMAX1107-7KW is a 19" rack mounted load bank designed to simulate IT server operation aspart of the testing and commissioning of the data hall and single phase power load testing of AC generators or UPS Systems. The unit incorporating light weight, force cooled high powerresistor elements. Adjustment of the load current is provided by front panel switch selection.The load bank incorporates several safety features. All units are light weight, robust, portableand carrving handles. The fan supply and the controls are powered from the power testsource and therefore the unit does not require an external auxiliary mains supply.


Specifications

Product name

230VAC-7kW Rack ounted l oad Bank

Use

The 7kW rack-mounted dual source AC load banks are used for IST commissioning in datacenter & data room. Testing both electrical network (UPS, Diesel generator, etc.) & airconditioning (free cooling, etc.), the rack-mounted load bank is simulating exact electrica & air conditioning impact of servers in the rack cabinet 19

Model number

IMAX1107-7KW

Electrical characteristics

Capacity

7kW resistive load

Design voltage

400/230VAC,3/1Ph, 50/60 Hz (Voltage+5%Acceptable)

Full load rating

Nominal: 7000W  30.4Amp @ 230VAC(Ph),10.10Amp @ 400VAC (3Ph)

Control switches

Main control switch with indication (Red)

Source ON/OFF switch with indication (Green)

Source Selector (Auto/Manual)

Load adjust

MCB (Schneider) for step control

Load steps

500W/500W/1000W/1000W/2000W/2000W

Minimum Step

500W

Input Source

Dual

Source Selection

Auto or Manual

Fan working source

Internal from testing power source

Protection

IP23

Duty cycle Connection

Continuous

Operation

3 x C20 panel sockets "2Set

Temperature Storage

0 to 40°C

Temperature

0 to 60°C

Ventilation

Cooling

Air is sucked in the front and blown out horizontally at the rear.

Air flow

Klixon on 85°C

Thermal protection

Red light alert (Over temperature)

Security

Auto shutoff load in the event of fan power supply failureEach load channels protected with MCB

Cooling

Air is sucked in the front and blown out horizontally at the rear.

Air flow

Klixon on 85°C

Mechanical characteristics

Technology

Expanded metal grids type insulated by ceramic rings

Housing

Steel

Height

Maximum 6U

Weight

Maximum 30kg

Movement

Front handles for slide in assembly to 19" rack

Length/Width

Should be rack mounted inside Telecommunication 42U cabinet

Element Type

High temperature ni chrome finned resistor elements


Products